Content Type  MooreHawke, a division of Moore Industries-International Inc., announces that the Route-Master Fieldbus System has ATEX approval (FM pending) as a redundant intrinsically-safe fieldbus system permitting the connection of any mix of Fieldbus Intrinsically Safe COncept (FISCO) and Entity devices. According to the company, this is the first fieldbus system approval to offer FISCO compatibility and power redundancy.

MooreHawke, a division of Moore Industries-International Inc., announces that the Route-Master Fieldbus System has ATEX approval (FM pending) as a redundant intrinsically-safe fieldbus system permitting the connection of any mix of Fieldbus Intrinsically Safe COncept (FISCO) and Entity devices. According to the company, this is the first fieldbus system approval to offer FISCO compatibility and power redundancy.

A Route-Master system consists of up to eight Trunk Isolator Modules in a 19-inch rack, each connected to one or more RM100 Fieldbus Device Couplers. This combination is now approved suitable for any mix of FISCO and Entity field devices. The RM100 Rack incorporates hot-swappable and load-sharing redundant DC power cards and full galvanic isolation. Intrinsically-safe approvals extend to IEC Gas Group IIC (NEC Groups A and B), with an industry-best 350m per segment.

The duplex FISCO Route-Master gives a calculated MTBF of 468 years, at least 5 times better than a conventional simplex FISCO system. Uniquely, it also allows the full Foundation Fieldbus network length of 1900m, and 120m spurs, double the normal FISCO restrictions.

RM100 Device Couplers have auto-resetting short-circuit protection, automatic segment termination to eliminate common installation errors and commissioning delays, and LED status indicators. MooreHawke's short circuit protection method prevents segment failure caused by multiple device faults. A unique "fold-back" technique automatically removes fault loads from the segment, and does not permit any current flow to those devices until faults are corrected. Manual termination is also offered at the user's request.


» No Comments
There are no comments up to now.
» Post Comment
Email (will not be published)
Name
Title
Comment
 remaining characters
Captcha Image Regenerate code when it's unreadable
 
newsletters - Choose a newsletter below and click on the "Sign Me Up" button.

To subscribe, select a newsletter from the options below and check the corresponding box.

Then, click the "Sign Me Up" button at the bottom of the box.

spacer

Once monthly. Don't miss intelligence
crucial to your job and business!
Sponsored Grey Star indicates a sponsored article that was submitted directly to this Web site by the supplier, and was not handled by the AW editorial staff.
Automation World may share your contact information with our sponsors, as detailed in our Privacy Policy.
Automation World will not share your information with a sponsor whose content you have not reviewed....
Feedback Form