Hurricane Season and Manufacturing Best Practices

Print
With certain areas of the United States still devastated by flooding and more tropical storms coming, Schneider Electric, (www.schneider-electric.com/us), is urging businesses to take every precaution with electrical equipment in preparation for the hurricane season.  
Below are some best practices on how to approach equipment that has met with some or considerabler water damage. Topics addressed are electrical equipment, interior component replacement, cleaning agents and abrasives and additional references.

Wet Electrical Equipment

Electrical equipment that has been submerged or come into contact with water must be replaced, though there are exceptions to this rule for larger equipment, which may be able to be reconditioned by trained factory service personnel. Equipment that may be reconditioned includes:
 

  • Switchboard enclosures and certain bus structures;
  • Switchgear;
  • Low-voltage power circuit breakers;
  • Medium-voltage circuit breakers;
  • Low-voltage bolted-pressure switches;
  • Medium-voltage switches;
  • Motor control center enclosures and bus structure;
  • Panelboard and load center enclosures;
  • Liquid-filled power transformers;
  • Cast-resin transformers; and,
  • Busway: epoxy coated bars.
     
Attempting to dry out the equipment (in many cases) leaves portions of the current-carrying parts with damp or wet surfaces. These surfaces may be in contact with insulators or other materials that prevent them
from being properly dried out and cleaned of debris.

Residual debris or wet surfaces may result in a loss of dielectric spacing within the equipment, and could present a hazard upon re-energization.

Equipment that must be replaced in its entirety is listed below:

  • Miniature and molded case circuit breakers;
  • Molded case switches;
  • Multi-metering equipment;
  • Safety switches (AC and DC);
  • Load centers or panelboard interiors;
  • Dry-type transformers;
  • Busway: mylar wrapped bars;
  • Solid state components;
  • Programmable logic controllers;
  • Fuses;
  • Electromechanical relays, contactors, starters, push buttons, limit switches, and other input logic and output controls;
  • Solid state motor starters;
  • Adjustable speed drives;
  • Motor control center components.
 

Equipment with Field Replaceable Interior Components

Generally, this type of replacement is limited to a load center or panelboard type of product where the entire assembly can be removed and replaced as a unit. In this case, there is a possibility that enclosures can be reused if they have not been subjected to physical damage and if they have been properly cleaned of all debris and foreign materials.
 

Cleaning Agents and Abrasives

Do not apply cleaning agents, particularly petroleum-based cleaners, to the current-carrying portions of electrical equipment to remove foreign debris, residues and other substances. Some cleaning and lubricating compounds can cause deterioration of the non-metallic insulating or structural portions of the equipment. Do not use abrasives such as sandpaper or steel wool to clean current-carrying parts of the equipment. These materials may remove plating or other conductive surfaces from the parts, which could result in a hazard when the equipment is re-energized.
 

Non-Submerged Equipment in Flooded Areas

Equipment in this situation should be inspected carefully by a qualified person to determine whether moisture has entered the enclosure. If any signs of moisture or damage exist, the equipment should be replaced or repaired.
 

Additional References:

NEMA Standard AB 4-2003, Guidelines for Inspection and Preventive Maintenance of Molded Case Circuit Breakers Used in Commercial andIndustrial Applications
NEMA Standard BU 1.1-2000, General Instructions for Proper Handling, Installation, Operation, and Maintenance of Busway Rated 600 Voltsor Less
NEMA Standard PB 1.1-2002, General Instructions for Proper Installation, Operation, and Maintenance of Panelboards Rated 600 Volts or Less
NEMA Standard PB 2.1-2002, General Instructions for Proper Handling, Installation, Operation, and Maintenance of Deadfront DistributionSwitchboards Rated 600 Volts or Less
NEMA Standard ICS 1.1-2003, Industrial Control and Systems: Safety Guidelines for the Application, Installation, and Maintenance of SolidState Controls
 

Grant Gerke ( ggerke@automationworld.com) is the Digital Managing Editor at Automation World magazine. 
 

Comments(0)

Add new comment

By submitting this form, you accept the Mollom privacy policy.

Follow Us

 

 

  NEWSLETTERS

Don’t miss intelligence crucial to your job and business!
Click on any newsletter to view a sample. Enter your email address below to sign up!

News Insights

News & Analysis

Product Insights

Latest Automation Products

TalkPoints

Automation Columnists

Feed Forward

Latest from Gary Mintchell

Automation Focus

Sponsored white papers, videos and products

Process Automation

Industry Trends & Applications

Motion Control

Machine & Motion Control

Automation Skills

Improve Industry Skills

Industrial
Ethernet Review

Network Application of IE

Packaging
Automation Review

Trends in Packaging Automation

Safety
Automation Insights

The How & Why of Safety

Each newsletter ranges in frequency from once per month to a few times per month at most.
Feedback Form